Single Phase Motor Full Load Amps Table |
| Full Load Amperes |
| Horsepower |
115 V |
208 V |
230 V |
Minimum
Transformer
KVA |
| 1/6 |
4.4 |
2.4 |
2.2 |
.53 |
| 1/4 |
5.8 |
3.2 |
2.9 |
.70 |
| 1/3 |
7.2 |
4.0 |
3.6 |
.87 |
| 1/2 |
9.8 |
5.4 |
4.9 |
1.18 |
| 3/4 |
13.8 |
7.6 |
6.9 |
1.66 |
| 1 |
16 |
8.8 |
8 |
1.92 |
| 1-1/2 |
20 |
11 |
10 |
2.40 |
| 2 |
24 |
13.2 |
12 |
2.88 |
| 3 |
34 |
18.7 |
17 |
4.10 |
| 5 |
56 |
30.8 |
28 |
6.72 |
| 7-1/2 |
80 |
44 |
40 |
9.6 |
| 10 |
100 |
55 |
50 |
12 |
(1) When motor service factor is greater than 1, increase full load
amps proportionally.
Example: If service factor is 1.15, increase above amp values by 15%. |
| Note: If motors are started more than once per hour add 20% additional KVA. |
| (Table by Acme Electric Corporation). |
|
|