| Home > Industry Tables & Calculators > Wiremold 500/700 Wire Capacities Data |
Wiremold 500/700 Wire Capacities Data |
| 400/800/2300 Raceway Wire Fill Capacity for Power |
| Cable/Wire Size |
O.D. |
400 Raceway |
800 Raceway |
| inches |
[mm] |
Number of Conductors |
Number of Conductors |
| 14 AWG |
0.111 |
[2.8] |
7 |
10 |
| 12 AWG |
0.130 |
[3.3] |
5 |
7 |
| 10 AWG |
0.164 |
[4.2] |
3 |
4 |
| 400/800/2300 Raceway Wire Fill Capacity for Communications |
| |
O.D. (Approx. Dia) |
500 Raceway |
700 Raceway |
| |
Cable wire Size |
inches |
[mm] |
20% Fill * |
40% Fill ** |
20% Fill * |
40% Fill ** |
UNSHIELDED TWISTED PAIR |
4-pair, 24 AWG, Cat 3 4-pair, 24 AWG, Cat 5e 4-pair, 24 AWG, Cat 6 |
0.190 0.210 0.250 |
[4.8] [5.3] [6.3] |
1 1 0 |
2 2 1 |
1 1 1 |
3 3 2 |
| TELEPHONE |
2-pair, 24 AWG 3-pair, 24 AWG 4-pair, 24 AWG 25-pair, 24 AWG |
0.140 0.150 0.190 0.410 |
[3.6] [3.8] [4.8] [10.4] |
2 2 1 0 |
2 2 1 0 |
3 2 1 0 |
6 5 3 0 |
| COAXIAL |
RG58/U RG59/U RG62/U RG6/U |
0.195 0.242 0.242 0.270 |
[5.0] [6.1] [6.1] [6.9] |
1 0 0 0 |
2 1 1 1 |
1 1 1 0 |
3 2 2 1 |
| TWINAXIAL |
100 Ohm |
0.330 |
[8.4] |
0 |
0 |
0 |
1 |
SHIELDED TWISTED PAIR |
Type 1 Type 2 Type 3 |
0.390 0.465 0.245 |
[9.9] [11.8] [6.2] |
0 0 0 |
0 0 1 |
0 0 1 |
0 0 2 |
| FIBER |
Mini ZipCord ZipCord Round 4 Strand Fiber Round 6 Strand Fiber |
0.079 x 0.157 0.118 x 0.236 0.187 0.256 |
[2 x 4] [3 x 6] [4.8] [6.5] |
3 1 1 0 |
6 1 1 1 |
4 1 1 1 |
8 3 3 2 |
| * 20% cable fill is calculated to approximate reduction in cable capacity due to connectors
mounted with raceway and fittings that may restrict cross sectional area. |
** 40% cable fill is the maximum designed cable fill based on a proposed revision to TIA/EIA 569-A.
|
|
|